111kN ANSI Class 52-5 Cap and Pin Type Porcelain Insulator from China Suppliers and Factory for Overhead Power Lines
Drawing
Product Specifications
| Suspension Type Anti-Pollution Insulator for High Voltage (ANSI) | ||||||||||
| Class ANSI | 52-1 | 52-2 | 52-3 | 52-4 | 52-5 | 52-6 | 52-9 | 52-10 | ||
| Main Dimensions (mm) | Diameter | 165 | 190.5 | 254 | 254 | 254 | 254 | 114 | 279.4 | |
| Height | 139.7 | 146 | 146 | 146 | 146 | 146 | 160 | 165 | ||
| Creepage Distance (mm) | 178 | 210 | 292 | 292 | 279 | 279 | 171 | 279 | ||
| Average Flashover Voltage | Power-frequency | Dry (kV) | 60 | 65 | 80 | 80 | 80 | 80 | 80 | 80 |
| Wet (kV) | 30 | 35 | 50 | 50 | 50 | 50 | 30 | 50 | ||
| Critical-Impulse 1.2/50μs Wave | Positive (kV) | 100 | 115 | 125 | 125 | 125 | 125 | 90 | 125 | |
| Negative (kV) | 100 | 115 | 130 | 130 | 130 | 130 | 100 | 130 | ||
| Radio-Influence-Voltage Data | Test Voltage to Ground (kV) | 7.5 | 7.5 | 10 | 10 | 10 | 10 | 7.5 | 10 | |
| Maximum RIV at 1000kHz (μV) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||
| Electro-mechanical Failing Load (kN) | 45 | 70 | 70 | 70 | 111 | 111 | 45 | 160 | ||
| Power-Frequency Puncture Voltage (kV) | 80 | 90 | 110 | 110 | 110 | 110 | 80 | 110 | ||
| Mechanical Impact Strength (N·m) | 5 | 6 | 6 | 6 | 7 | 7 | 5 | 10 | ||
| Time Load Test Value (kN) | 27 | 44 | 44 | 44 | 67 | 67 | 27 | 107 | ||
Certificate
Packaging
Frequently Asked Questions (FAQ)
Q What ANSI classes are covered under this suspension insulator series?
This product line includes ANSI Class 52-1, 52-2, 52-3, 52-4, 52-5, 52-6, 52-9, and 52-10, accommodating diverse transmission voltage and mechanical strength specifications.
Q What is the maximum electro-mechanical failing load available for these models?
The electro-mechanical failing load ranges from 45 kN up to 160 kN (Class 52-10), ensuring structural reliability for various high-voltage suspension configurations.
Q How do these anti-pollution insulators prevent flashover in contaminated environments?
The units feature optimized creepage distances up to 292 mm and high power-frequency puncture ratings (up to 110 kV) to minimize leakage currents and prevent flashovers under severe atmospheric pollution.
Q What packaging measures are used to prevent damage during long-distance shipping?
JIANGXI NEW ELECTRIC CO., LTD. employs multi-layer protection including waterproof/moisture-proof inner wrapping and drop-tested thickened solid wood or plywood outer crates suitable for sea, land, and air freight.
Q What are the Radio-Influence-Voltage (RIV) specifications for this insulator series?
All models maintain a maximum RIV of 50 μV at 1000 kHz under ground test voltages ranging from 7.5 kV to 10 kV, minimizing electromagnetic interference.