Drawing
Product Specifications
| Suspension Type Anti-Pollution Insulator for High Voltage (ANSI) | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Class ANSI | 52-1 | 52-2 | 52-3 | 52-4 | 52-5 | 52-6 | 52-9 | 52-10 | ||
| Main Dimensions (mm) | Diameter | 165 | 190.5 | 254 | 254 | 254 | 254 | 114 | 279.4 | |
| Height | 139.7 | 146 | 146 | 146 | 146 | 146 | 160 | 165 | ||
| Creepage Distance(mm) | 178 | 210 | 292 | 292 | 279 | 279 | 171 | 279 | ||
| Average Flashover Voltage | Power-frequency | Dry(kV) | 60 | 65 | 80 | 80 | 80 | 80 | 80 | 80 |
| Wet(kV) | 30 | 35 | 50 | 50 | 50 | 50 | 30 | 50 | ||
| Critical-Impulse 1.2x50μs | Positive (kV) | 100 | 115 | 125 | 125 | 125 | 125 | 90 | 125 | |
| Negative(kV) | 100 | 115 | 130 | 130 | 130 | 130 | 100 | 130 | ||
| Radio-Influence Data | Test Voltage (kV) | 7.5 | 7.5 | 10 | 10 | 10 | 10 | 7.5 | 10 | |
| Max RIV @ 1000kHz (μV) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||
| Electro-mechanical Failing Load (kN) | 45 | 70 | 70 | 70 | 111 | 111 | 45 | 160 | ||
| Power-Frequency Puncture Voltage (kV) | 80 | 90 | 110 | 110 | 110 | 110 | 80 | 110 | ||
| Mechanical Impact Strength (n.m) | 5 | 6 | 6 | 6 | 7 | 7 | 5 | 10 | ||
| Time Load Test Value (kn) | 27 | 44 | 44 | 44 | 67 | 67 | 27 | 107 | ||
Certificate
JIANGXI NEW ELECTRIC CO., LTD. (Jiangxi NE) ‘s products have obtained a series of ISO management system certifications and have been certified by multiple CNAS-accredited testing institutions worldwide, including the National High Voltage Electrical Apparatus Quality Supervision and Inspection Center (Xi'an), the National Electrical Product Quality Supervision and Inspection Center (Jiangsu), the India Power Grid Laboratory, and the Brazilian National Laboratory. These achievements make our products highly trustworthy for customers worldwide.
Packaging
Frequently Asked Questions
What is the primary use of Suspension Type Anti-Pollution Insulators?
These insulators are designed for high-voltage transmission lines, specifically in areas with high pollution levels. They provide excellent electrical insulation and mechanical support while resisting environmental contaminants.
Do your insulators comply with international standards?
Yes, our products are designed and tested according to ANSI standards (e.g., ANSI 52-1 to 52-10) and have received certifications from various international CNAS-accredited laboratories.
What does "Creepage Distance" signify in your specifications?
Creepage distance is the shortest path along the surface of the insulation material between two conductive parts. A higher creepage distance improves the insulator's performance in polluted or wet conditions.
Which testing institutions have certified Jiangxi New Electric products?
Our products are certified by the National High Voltage Electrical Apparatus Quality Supervision and Inspection Center (Xi'an), India Power Grid Laboratory, and the Brazilian National Laboratory, among others.
How do you ensure the mechanical strength of the insulators?
Each product class undergoes rigorous Electro-mechanical Failing Load tests and Mechanical Impact Strength tests to ensure they can withstand the physical stresses of high-voltage power lines.
How are the products protected during shipping?
We use professional-grade industrial packaging designed for international transit, ensuring that the insulators remain intact and free from mechanical damage or surface contamination during delivery.