| Suspension Type Anti-Pollution Insulator for High Voltage (ANSI) | ||||||||||
| Class ANSI | 52-1 | 52-2 | 52-3 | 52-4 | 52-5 | 52-6 | 52-9 | 52-10 | ||
| Main Dimensions (mm) | Diameter | 165 | 190.5 | 254 | 254 | 254 | 254 | 114 | 279.4 | |
| Height | 139.7 | 146 | 146 | 146 | 146 | 146 | 160 | 165 | ||
| Creepage Distance(mm) | 178 | 210 | 292 | 292 | 279 | 279 | 171 | 279 | ||
| Average Flashover Voltage | Power-frequency | Dry(kV) | 60 | 65 | 80 | 80 | 80 | 80 | 80 | 80 |
| Wet(kV) | 30 | 35 | 50 | 50 | 50 | 50 | 30 | 50 | ||
| Critical-Impulse 1.2x50μs Wave | Positive (kV) | 100 | 115 | 125 | 125 | 125 | 125 | 90 | 125 | |
| Negative(kV) | 100 | 115 | 130 | 130 | 130 | 130 | 100 | 130 | ||
| Radio-Influence-Voltage Data | Test Voltage to Ground(kV) | 7.5 | 7.5 | 10 | 10 | 10 | 10 | 7.5 | 10 | |
| Maximum RIV at 1000kHz (μV) | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||
| Electro-mechanical Failing Load (kN) | 45 | 70 | 70 | 70 | 111 | 111 | 45 | 160 | ||
| Power-Frequency Puncture Voltage (kV) | 80 | 90 | 110 | 110 | 110 | 110 | 80 | 110 | ||
| Mechanical Impact Strength (N.m) | 5 | 6 | 6 | 6 | 7 | 7 | 5 | 10 | ||
| Time Load Test Value (kN) | 27 | 44 | 44 | 44 | 67 | 67 | 27 | 107 | ||
Certificate
The Products of JIANGXI NEW ELECTRIC CO., LTD. Have obtained a series of ISO certification. Strict quality inspection system fully guarantees product quality. We adhere to independent R&D and hold multiple invention patents with outstanding innovation strength. With excellent quality and technological advantages, our products are exported worldwide and highly acknowledged by overseas markets.
Packaging
Frequently Asked Questions
1. What standards do your suspension insulators comply with?
Our suspension type anti-pollution insulators are designed and tested to meet ANSI standards, ensuring high reliability for high-voltage applications.
2. What is the electro-mechanical failing load range?
Depending on the specific ANSI class (52-1 to 52-10), the failing load ranges from 45 kN up to 160 kN.
3. How does the anti-pollution design benefit high-voltage lines?
The design increases the creepage distance (up to 292mm for some classes), which prevents flashover in environments with high humidity, salt, or dust.
4. What quality certifications does Jiangxi New Electric Co., Ltd. hold?
We have obtained a series of ISO certifications and hold multiple invention patents, supported by a strict quality inspection system.
5. Are the products suitable for international export?
Yes, our products are exported worldwide and are highly acknowledged in overseas markets for their technological advantages and excellent quality.
6. What is the typical packaging for these insulators?
We use professional industrial packaging to ensure that the insulators are protected from mechanical impact and environmental factors during transit.