ANSI Standard 52-9 Suspension Cap and Pin Type Porcelain Ceramic Insulator with Clevis for Power Transmission Line
Drawing
Product Specifications
|
Suspension Type Anti-Pollution Insulator for High Voltage (ANSI) |
||||||||||
|
Class ANSI |
52-1 |
52-2 |
52-3 |
52-4 |
52-5 |
52-6 |
52-9 |
52-10 |
||
|
Main Dimensions (mm) |
Diameter |
165 |
190.5 |
254 |
254 |
254 |
254 |
114 |
279.4 |
|
|
Height |
139.7 |
146 |
146 |
146 |
146 |
146 |
160 |
165 |
||
|
Creepage Distance(mm) |
178 |
210 |
292 |
292 |
279 |
279 |
171 |
279 |
||
|
Average Flashover Voltage |
Power-frequency |
Dry(kV) |
60 |
65 |
80 |
80 |
80 |
80 |
80 |
80 |
|
Wet(kV) |
30 |
35 |
50 |
50 |
50 |
50 |
30 |
50 |
||
|
Critical-Impulse 15x40μs Wave |
Positive (kV) |
100 |
115 |
125 |
125 |
125 |
125 |
90 |
125 |
|
|
Negative(kV) |
100 |
115 |
130 |
130 |
130 |
130 |
100 |
130 |
||
|
Radio-Influence-Voltage Data |
Test Voltage to Ground(kV) |
7.5 |
7.5 |
10 |
10 |
10 |
10 |
7.5 |
10 |
|
|
Maximum RIV at 1000kHz (μV) |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
||
|
Electro-mechanical Failing Load (kN) |
45 |
70 |
70 |
70 |
111 |
111 |
45 |
160 |
||
|
Power-Frequency Puncture Voltage (kV) |
80 |
90 |
110 |
110 |
110 |
110 |
80 |
110 |
||
|
Mechanical Impact Strength (n.m) |
5 |
6 |
6 |
6 |
7 |
7 |
5 |
10 |
||
|
Time Load Test Value (kn) |
27 |
44 |
44 |
44 |
67 |
67 |
27 |
107 |
||
Certificate
Packaging