ANSI Standard 56-3 High Voltage Pin Type Porcelain Ceramic Insulator for Electrical Power System
Drawing
Product Specifications
|
High Voltage Pin Type Insulators (ANSI C29.6 Standard) |
|||||||
|
ANSI Class |
56-1 |
56-2 |
56-3 |
56-4 |
56-5 |
||
|
Main Dimensions (mm) |
D |
191 |
229 |
267 |
305 |
343 |
|
|
H |
146 |
165 |
191 |
241 |
318 |
||
|
d |
89 |
102 |
102 |
- |
- |
||
|
d1 |
35 |
35 |
35 |
35 |
35 |
||
|
h |
51 |
51 |
51 |
51 |
51 |
||
|
R1 |
19 |
19 |
19 |
19 |
19 |
||
|
R2 |
14 |
14 |
14 |
14 |
14 |
||
|
Creepage Distance (mm) |
330 |
432 |
333 |
685 |
864 |
||
|
Min. Pin Length (mm) |
152 |
178 |
203 |
254 |
305 |
||
|
Cantilever Strength (kN) |
11 |
13.2 |
13.2 |
13.2 |
13.2 |
||
|
Flashover Voltage |
Power Frequency (kV) |
Dry |
95 |
110 |
125 |
140 |
175 |
|
Wet |
60 |
70 |
80 |
95 |
125 |
||
|
Impulse (kV) |
Positive |
150 |
175 |
200 |
225 |
270 |
|
|
Negative |
190 |
225 |
265 |
310 |
340 |
||
|
Power Frequency Puncture Voltage (kV) |
130 |
145 |
165 |
185 |
225 |
||
|
Radio Influence Voltage |
Test Voltage to Ground(kV) |
15 |
22 |
30 |
30 |
44 |
|
|
Max. RIV at 1 MHz(μV) |
100 |
100 |
200 |
200 |
200 |
||
|
Weight (kg) |
3.7 |
5.3 |
7 |
10.8 |
13.5 |
||
Certificate
Our products are certified by ISO. We strictly control the whole production process with solid quality standards. Favored by domestic customers, our products are also sold worldwide and enjoy high reputation globally.
Packaging