ANSI Standard 56-3 High Voltage Pin Type Porcelain Insulator for 35kV Power Lines | China Suppliers & Factory
Drawing
Product Specifications
| High Voltage Pin Type Insulators (ANSI C29.6 Standard) | |||||||
| ANSI Class | 56-1 | 56-2 | 56-3 | 56-4 | 56-5 | ||
| Main Dimensions (mm) | D | 191 | 229 | 267 | 305 | 343 | |
| H | 146 | 165 | 191 | 241 | 318 | ||
| d | 89 | 102 | 102 | - | - | ||
| d1 | 35 | 35 | 35 | 35 | 35 | ||
| h | 51 | 51 | 51 | 51 | 51 | ||
| R1 | 19 | 19 | 19 | 19 | 19 | ||
| R2 | 14 | 14 | 14 | 14 | 14 | ||
| Creepage Distance (mm) | 330 | 432 | 333 | 685 | 864 | ||
| Min. Pin Length (mm) | 152 | 178 | 203 | 254 | 305 | ||
| Cantilever Strength (kN) | 11 | 13.2 | 13.2 | 13.2 | 13.2 | ||
| Flashover Voltage | Power Frequency (kV) | Dry | 95 | 110 | 125 | 140 | 175 |
| Wet | 60 | 70 | 80 | 95 | 125 | ||
| Impulse (kV) | Positive | 150 | 175 | 200 | 225 | 270 | |
| Negative | 190 | 225 | 265 | 310 | 340 | ||
| Power Frequency Puncture Voltage (kV) | 130 | 145 | 165 | 185 | 225 | ||
| Radio Influence Voltage | Test Voltage to Ground(kV) | 15 | 22 | 30 | 30 | 44 | |
| Max. RIV at 1 MHz(μV) | 100 | 100 | 200 | 200 | 200 | ||
| Weight (kg) | 3.7 | 5.3 | 7 | 10.8 | 13.5 | ||
Certificate
Our products are certified by ISO. We strictly control the whole production process with solid quality standards. Favored by domestic customers, our products are also sold worldwide and enjoy high reputation globally.
Packaging
Frequently Asked Questions
What standard do these High Voltage Pin Type Insulators follow?
Our insulators are manufactured in strict accordance with the ANSI C29.6 standard, ensuring reliability and compatibility for high-voltage applications.
What is the cantilever strength of the 56 series insulators?
The cantilever strength ranges from 11 kN for the ANSI 56-1 class to 13.2 kN for classes 56-2 through 56-5.
Are your production processes quality certified?
Yes, our products and production processes are ISO certified. we maintain rigorous quality control standards from raw material to finished product.
What is the maximum creepage distance available?
The creepage distance varies by model, reaching up to 864 mm for the ANSI 56-5 class insulator.
How do you handle Radio Influence Voltage (RIV)?
Our insulators are tested for RIV at 1 MHz, with maximum values ranging between 100μV and 200μV depending on the specific model and test voltage.
Do you export these insulators globally?
Yes, our high-voltage insulators are sold worldwide and have earned a high reputation globally due to their performance and durability.