High Voltage ANSI Standard 56-3 Pin Type Porcelain Insulator - China Suppliers & Factory for 35kV Power Systems
Drawing
Product Specifications
| High Voltage Pin Type Insulators (ANSI C29.6 Standard) | |||||||
ANSI Class |
56-1 | 56-2 | 56-3 | 56-4 | 56-5 | ||
Main Dimensions (mm) |
D | 191 | 229 | 267 | 305 | 343 | |
| H | 146 | 165 | 191 | 241 | 318 | ||
| d | 89 | 102 | 102 | - | - | ||
| d1 | 35 | 35 | 35 | 35 | 35 | ||
| h | 51 | 51 | 51 | 51 | 51 | ||
| R1 | 19 | 19 | 19 | 19 | 19 | ||
| R2 | 14 | 14 | 14 | 14 | 14 | ||
Creepage Distance (mm) |
330 | 432 | 333 | 685 | 864 | ||
Min. Pin Length (mm) |
152 | 178 | 203 | 254 | 305 | ||
Cantilever Strength (kN) |
11 | 13.2 | 13.2 | 13.2 | 13.2 | ||
Flashover Voltage |
Power Frequency (kV) | Dry | 95 | 110 | 125 | 140 | 175 |
| Wet | 60 | 70 | 80 | 95 | 125 | ||
| Impulse (kV) | Positive | 150 | 175 | 200 | 225 | 270 | |
| Negative | 190 | 225 | 265 | 310 | 340 | ||
Power Frequency Puncture Voltage (kV) |
130 | 145 | 165 | 185 | 225 | ||
Radio Influence Voltage |
Test Voltage to Ground(kV) | 15 | 22 | 30 | 30 | 44 | |
| Max. RIV at 1 MHz(μV) | 100 | 100 | 200 | 200 | 200 | ||
Weight (kg) |
3.7 | 5.3 | 7 | 10.8 | 13.5 | ||
Certificate
Our products are certified by ISO. We strictly control the whole production process with solid quality standards. Favored by domestic customers, our products are also sold worldwide and enjoy high reputation globally.
Packaging
Frequently Asked Questions
What standards do these pin type insulators comply with?
These high voltage pin type insulators are manufactured in strict accordance with the ANSI C29.6 standard.
What is the cantilever strength of the 56 series insulators?
The cantilever strength ranges from 11 kN for class 56-1 to 13.2 kN for classes 56-2 through 56-5.
Are your manufacturing processes certified?
Yes, our production processes are ISO certified, ensuring strict quality control and global reputation.
What is the maximum creepage distance available?
The maximum creepage distance in this series is 864 mm, which is provided by the ANSI Class 56-5 insulator.
How is the Radio Influence Voltage (RIV) tested?
It is measured as Max RIV at 1 MHz, with test voltages to ground ranging from 15 kV up to 44 kV depending on the insulator class.