Physical Dimensions
- Height (H):108 mm (4.375 in)
- Diameter (D):73 mm (approx. 2-3/8 in to 2-7/8 in)
- Maximum Cable Diameter:1/2 in
- Net Weight:65 kg (1.8 lbs depending on manufacturer specs like Hubbell-Chance)
Application & Safety Design
- Primary Use:Commonly deployed on 11 kV overhead distribution lines and utility poles to support stay/guy wires.
- Interlocking Safety Feature:Designed with an interlinked shape so that even if the porcelain dielectric cracks or breaks under extreme mechanical stress, the guy-wire loops remain interlocked and will not completely fall to the ground.

|
Stay Porcelain Insulator(ANSI Standard) |
|||||
|
Type |
54-1 |
54-2 |
54-3 |
54-4 |
|
|
Fig. |
1 |
1 |
1 |
2 |
|
|
Creepage Distance(mm) |
41 |
48 |
57 |
76 |
|
|
Tensile Strength(kN) |
44 |
53 |
89 |
89 |
|
|
Power Frequency Voltage 50Hz(kV) |
Dry |
25 |
30 |
35 |
40 |
|
|
Wet |
12 |
15 |
18 |
23 |
|
Main Dimension(mm) |
H |
89 |
108 |
140 |
172 |
|
|
h |
44 |
57 |
67 |
79 |
|
|
h1 |
64 |
76 |
103 |
114 |
|
|
D |
64 |
73 |
86 |
89 |
|
|
d |
44 |
54 |
60 |
60 |
|
|
d1 |
16 |
22 |
25 |
25 |
|
Weight(kg) |
0.5 |
0.65 |
1.2 |
1.85 |
|
|
Applicable Standard |
ANSI C29.4 |
||||